Overview
This NEMA 4X control panel is intended to control and protect a compatible cooling tower basin-heater system. Select the complete voltage/phase catalog suffix and panel ampacity for the connected heater load.
Electrical Specifications
- Catalog base number: 874Z-2173
- Maximum panel current: 64 A
- Control: Preset 45°F printed-circuit-board control with dual-sensing probe
- Panel configuration: Circuit breaker
- Enclosure: NEMA 4X with pre-mounted conduit hubs
- Ambient operating range: -10°F to 104°F
- Voltage and phase: Selected by the completed catalog-number suffix; refer to the manufacturer load table
Control Features
- Single probe senses both basin water temperature and water level
- 12 ft outdoor-rated probe cord and PVC basin-wall hub connector
- Fail-safe output de-energizes if the sensor circuit is open or shorted
- Remote interlock terminal block
- 316 stainless steel probe tubing with 304 stainless steel fitting; horizontal or vertical installation; 15 psi rating
Compatible Basin Heaters
Use with basin heaters whose total connected load does not exceed this panel rating at the selected voltage and phase. Confirm the completed panel catalog number and heater load against the manufacturer table.
Documents
See the attached manufacturer control-panel datasheet for catalog-number suffixes, maximum kW by voltage/phase, enclosure sizing, and available options.