120 Volt, 8 Watt per Foot self-regulating heat trace cable with tinned copper braid and fluoropolymer overjacket. For pipe freeze protection and low-temperature process maintenance up to 150°F. Cut to length in the field.

Wattage
8 Watt
Buy 1000' $6.59
Buy 5000' $5.92

Enter how many feet you want to order. Cable is cut to length.

HTR Low-Temperature Self-Regulating Heat Trace

The 8HTR1-CT provides temperature-responsive heat for pipe freeze protection and low-temperature process maintenance. Its CT construction is suitable where a fluoropolymer overjacket is required.

Technical Specifications

Series
HTR
SKU
8HTR1-CT
Watt Density
8 W/ft at 50°F (10°C)
Nominal Voltage
120 Volt
Manufacturer Supply Voltage
110–120 VAC
Cable Type
Self-Regulating
Bus Wire
Tinned Copper, 14 AWG / 16 AWG
Braid
Tinned Copper
Outer Jacket
Fluoropolymer (CT)
Maximum Maintenance Temperature
150°F (65°C)
Intermittent Exposure Temperature
185°F (85°C)
Temperature Classification
T5/T6
Minimum Bend Radius
30 mm
Cut to Length
Yes
Field Termination
Yes
Cable Overlap
Permitted
Ground-Fault Protection
Required

Maximum Circuit Length

8HTR1-CT — 120 V, 8 W/ft

Minimum Startup Temperature 16 A 20 A 25 A 32 A 40 A
50°F (10°C) 185 ft 202 ft 205 ft 205 ft 205 ft
32°F (0°C) 163 ft 185 ft 205 ft 205 ft 205 ft
14°F (-10°C) 145 ft 163 ft 205 ft 205 ft 205 ft
-4°F (-20°C) 116 ft 149 ft 205 ft 205 ft 205 ft
-40°F (-40°C) 103 ft 130 ft 192 ft 205 ft 205 ft

Maximum circuit length depends on breaker size and minimum startup temperature.

Construction

Parallel tinned-copper bus wires and a PTC self-regulating conductive core are covered by modified-polyolefin inner insulation, tinned-copper braid, and a fluoropolymer overjacket.

HTR Cable Selection

Compare published CR thermoplastic and CT fluoropolymer HTR constructions.

Part Number Output Voltage Construction
3HTR1-CR 3 W/ft 120 V Tinned Copper Braid + Modified Polyolefin Overjacket (CR)
3HTR2-CR 3 W/ft 240 V Tinned Copper Braid + Modified Polyolefin Overjacket (CR)
5HTR1-CR 5 W/ft 120 V Tinned Copper Braid + Modified Polyolefin Overjacket (CR)
5HTR2-CR 5 W/ft 240 V Tinned Copper Braid + Modified Polyolefin Overjacket (CR)
8HTR1-CR 8 W/ft 120 V Tinned Copper Braid + Modified Polyolefin Overjacket (CR)
8HTR2-CR 8 W/ft 240 V Tinned Copper Braid + Modified Polyolefin Overjacket (CR)
10HTR1-CR 10 W/ft 120 V Tinned Copper Braid + Modified Polyolefin Overjacket (CR)
10HTR2-CR 10 W/ft 240 V Tinned Copper Braid + Modified Polyolefin Overjacket (CR)
12HTR1-CR 12 W/ft 120 V Tinned Copper Braid + Modified Polyolefin Overjacket (CR)
12HTR2-CR 12 W/ft 240 V Tinned Copper Braid + Modified Polyolefin Overjacket (CR)
3HTR1-CT 3 W/ft 120 V Tinned Copper Braid + Fluoropolymer Overjacket (CT)
3HTR2-CT 3 W/ft 240 V Tinned Copper Braid + Fluoropolymer Overjacket (CT)
5HTR1-CT 5 W/ft 120 V Tinned Copper Braid + Fluoropolymer Overjacket (CT)
5HTR2-CT 5 W/ft 240 V Tinned Copper Braid + Fluoropolymer Overjacket (CT)
8HTR1-CTCurrent Product 8 W/ft 120 V Tinned Copper Braid + Fluoropolymer Overjacket (CT)
8HTR2-CT 8 W/ft 240 V Tinned Copper Braid + Fluoropolymer Overjacket (CT)
10HTR1-CT 10 W/ft 120 V Tinned Copper Braid + Fluoropolymer Overjacket (CT)
10HTR2-CT 10 W/ft 240 V Tinned Copper Braid + Fluoropolymer Overjacket (CT)
12HTR1-CT 12 W/ft 120 V Tinned Copper Braid + Fluoropolymer Overjacket (CT)
12HTR2-CT 12 W/ft 240 V Tinned Copper Braid + Fluoropolymer Overjacket (CT)

Installation Notes

  • Cut and terminate in the field using compatible HTR connection and termination components.
  • Use the applicable circuit-length table for the selected startup temperature and Type C breaker.
  • Ground the metallic braid and provide code-compliant ground-fault protection.
  • Cable overlap is permitted by the HTR manufacturer.

Sizing water-pipe freeze protection? Use the Pipe Freeze Protection Configurator.

Complete the Cable System

Connection, termination, installation, and control products selected for HTR Series cable. Verify electrical ratings and installation requirements for the exact circuit.

Connection and installation accessories

Controllers and thermostats

Choose ambient or line sensing and confirm voltage, circuit load, sensor, enclosure, and ground-fault requirements.