5 Watt per Foot 240 Volt Self-Regulating Heat Trace Cable – Thermoplastic Overjacket over Metal Braid – HTR

Part Number: 5HTR2-CR

In Stock: 10,829 FT

$5.42 per ft

Installation Kits, Accessories & ControllersInstallation Kits, Accessories & Controllers →
Freeze Protection Configurator

Build a complete freeze-protection system for water piping.

240 Volt, 5 Watt per Foot self-regulating heat trace cable with tinned copper braid and modified-polyolefin thermoplastic overjacket. For pipe freeze protection and low-temperature process maintenance up to 150°F. Cut to length in the field.

Wattage
5 Watt
Buy 1000' $4.82
Buy 5000' $4.34

Enter how many feet you want to order. Cable is cut to length.

HTR Low-Temperature Self-Regulating Heat Trace

The 5HTR2-CR provides temperature-responsive heat for pipe freeze protection and low-temperature process maintenance. Its CR construction uses a modified-polyolefin thermoplastic overjacket for general industrial environments.

Technical Specifications

Series
HTR
SKU
5HTR2-CR
Watt Density
5 W/ft at 50°F (10°C)
Nominal Voltage
240 Volt
Manufacturer Supply Voltage
220–240 VAC
Cable Type
Self-Regulating
Bus Wire
Tinned Copper, 14 AWG / 16 AWG
Braid
Tinned Copper
Outer Jacket
Modified Polyolefin Thermoplastic (CR)
Maximum Maintenance Temperature
150°F (65°C)
Intermittent Exposure Temperature
185°F (85°C)
Temperature Classification
T5/T6
Minimum Bend Radius
30 mm
Cut to Length
Yes
Field Termination
Yes
Cable Overlap
Permitted
Ground-Fault Protection
Required

Maximum Circuit Length

5HTR2-CR — 240 V, 5 W/ft

Minimum Startup Temperature 16 A 20 A 25 A 32 A 40 A
50°F (10°C) 555 ft 555 ft 555 ft 555 ft 555 ft
32°F (0°C) 507 ft 555 ft 555 ft 555 ft 555 ft
14°F (-10°C) 455 ft 520 ft 555 ft 555 ft 555 ft
-4°F (-20°C) 383 ft 483 ft 555 ft 555 ft 555 ft
-40°F (-40°C) 294 ft 421 ft 555 ft 555 ft 555 ft

Maximum circuit length depends on breaker size and minimum startup temperature.

Construction

Parallel tinned-copper bus wires and a PTC self-regulating conductive core are covered by modified-polyolefin inner insulation, tinned-copper braid, and a modified-polyolefin thermoplastic overjacket.

HTR Cable Selection

Compare published CR thermoplastic and CT fluoropolymer HTR constructions.

Part Number Output Voltage Construction
3HTR1-CR 3 W/ft 120 V Tinned Copper Braid + Modified Polyolefin Overjacket (CR)
3HTR2-CR 3 W/ft 240 V Tinned Copper Braid + Modified Polyolefin Overjacket (CR)
5HTR1-CR 5 W/ft 120 V Tinned Copper Braid + Modified Polyolefin Overjacket (CR)
5HTR2-CRCurrent Product 5 W/ft 240 V Tinned Copper Braid + Modified Polyolefin Overjacket (CR)
8HTR1-CR 8 W/ft 120 V Tinned Copper Braid + Modified Polyolefin Overjacket (CR)
8HTR2-CR 8 W/ft 240 V Tinned Copper Braid + Modified Polyolefin Overjacket (CR)
10HTR1-CR 10 W/ft 120 V Tinned Copper Braid + Modified Polyolefin Overjacket (CR)
10HTR2-CR 10 W/ft 240 V Tinned Copper Braid + Modified Polyolefin Overjacket (CR)
12HTR1-CR 12 W/ft 120 V Tinned Copper Braid + Modified Polyolefin Overjacket (CR)
12HTR2-CR 12 W/ft 240 V Tinned Copper Braid + Modified Polyolefin Overjacket (CR)
3HTR1-CT 3 W/ft 120 V Tinned Copper Braid + Fluoropolymer Overjacket (CT)
3HTR2-CT 3 W/ft 240 V Tinned Copper Braid + Fluoropolymer Overjacket (CT)
5HTR1-CT 5 W/ft 120 V Tinned Copper Braid + Fluoropolymer Overjacket (CT)
5HTR2-CT 5 W/ft 240 V Tinned Copper Braid + Fluoropolymer Overjacket (CT)
8HTR1-CT 8 W/ft 120 V Tinned Copper Braid + Fluoropolymer Overjacket (CT)
8HTR2-CT 8 W/ft 240 V Tinned Copper Braid + Fluoropolymer Overjacket (CT)
10HTR1-CT 10 W/ft 120 V Tinned Copper Braid + Fluoropolymer Overjacket (CT)
10HTR2-CT 10 W/ft 240 V Tinned Copper Braid + Fluoropolymer Overjacket (CT)
12HTR1-CT 12 W/ft 120 V Tinned Copper Braid + Fluoropolymer Overjacket (CT)
12HTR2-CT 12 W/ft 240 V Tinned Copper Braid + Fluoropolymer Overjacket (CT)

Installation Notes

  • Cut and terminate in the field using compatible HTR components.
  • Use the applicable circuit-length table and ground the metallic braid.
  • Provide code-compliant ground-fault protection. Cable overlap is manufacturer permitted.

Sizing water-pipe freeze protection? Use the Pipe Freeze Protection Configurator.

Complete the Cable System

Connection, termination, installation, and control products selected for HTR Series cable. Verify electrical ratings and installation requirements for the exact circuit.

Connection and installation accessories

Controllers and thermostats

Choose ambient or line sensing and confirm voltage, circuit load, sensor, enclosure, and ground-fault requirements.