5 Watt per Foot 240 Volt Self-Regulating Hazardous Location Heat Trace Cable – Fluoropolymer Overjacket – HSRL

Part Number: HSRL5-2CT

Availability: In stock

$25.05 per ft

Installation Kits, Accessories & ControllersInstallation Kits, Accessories & Controllers →

240 Volt, 5 Watt per Foot self-regulating heat trace cable with tinned copper braid and fluoropolymer overjacket for Division 1 hazardous locations. For pipe freeze protection and process temperature maintenance up to 150°F. Cut to length in the field.

Wattage
5 Watt
Minimum Quantity
50

Enter how many feet you want to order. Cable is cut to length.

HSRL Hazardous-Location Self-Regulating Heat Trace

Chromalox HSRL5-2CT is low-temperature self-regulating cable for freeze protection and process maintenance in the specified Division 1 hazardous locations. It can be field cut up to its maximum circuit length.

Technical Specifications

Series
HSRL
Manufacturer
Chromalox
Technology
Self-Regulating
Watt Density
5 W/ft at 50°F
Nominal HEP Voltage
240 V
Manufacturer Voltage
208–277 V
Bus Wire
Twin 16 AWG Copper
Inner Jacket
Polyolefin
Braid
Tinned Copper
Outer Jacket
High-Temperature Fluoropolymer Overjacket
Maximum Maintain Temperature
150°F (65°C)
Maximum Exposure, Power Off
185°F (85°C)
Minimum Bend Radius
1-1/8 in
Approximate Size
3/8 in W × 1/8 in H
Pipe
Metal & Plastic
Cut to Length
Yes
Overlap
Single overlap permitted
Ground-Fault Protection
Required; 30 mA minimum trip recommended
Temperature Class
T5

Output at Alternate Supply Voltages

208 V 220 V 277 V
4.1 (-18%) W/ft 4.5 (-10%) W/ft 5.6 (+13%) W/ft

Hazardous Location Approvals

FM Approved: Class I, Division 1, Groups B, C, D; Class II, Division 1, Groups E, F, G; Class III, Division 1.

CSA Approved: Class I, Division 1, Groups B, C, D; Class II, Division 1, Groups E, F, G.

Maximum Circuit Length

HSRL5-2CT — 240 V nominal, 5 W/ft

Minimum Startup Temperature 10 A 15 A 20 A 25 A 30 A 40 A
50°F 250 ft 375 ft 505 ft 540 ft NR NR
0°F 180 ft 270 ft 360 ft 450 ft 540 ft NR
-20°F 160 ft 245 ft 325 ft 405 ft 490 ft 540 ft

NR = Not Required; maximum circuit length is reached with a smaller breaker size. Maximum circuit length depends on breaker size and minimum startup temperature.

Construction

Twin 16 AWG copper bus wires are embedded in a semiconductive polymer self-regulating core. A polyolefin insulating jacket, tinned-copper grounding braid, and high-temperature fluoropolymer corrosion-resistant overjacket complete the construction.

HSRL Cable Selection

Part Number Output HEP Nominal Voltage Temperature Class
HSRL3-1CT 3 W/ft 120 V T6
HSRL3-2CT 3 W/ft 240 V T6
HSRL5-1CT 5 W/ft 120 V T5
HSRL5-2CTCurrent Product 5 W/ft 240 V T5
HSRL10-1CT 10 W/ft 120 V T4A
HSRL8-2CT 8 W/ft 240 V T5
HSRL10-2CT 10 W/ft 240 V T4A
HSRL8-1CT 8 W/ft 120 V T5

Installation / Hazardous-Area Notes

  • Cut to length in the field up to the applicable maximum circuit length.
  • Use listed Chromalox HL connection components and ground the metallic braid.
  • Provide code-compliant ground-fault protection; Chromalox recommends a 30 mA minimum trip level to reduce nuisance tripping.
  • A single cable overlap is permitted without burnout.

For preliminary water-pipe freeze-protection sizing, use the Pipe Freeze Protection Configurator; Division 1 selection still requires engineering consultation.

Complete the Cable System

Hazardous-location connection components, monitor lights, sensors, and controls for this cable family. Confirm the exact area classification and product approval before ordering.

Connection and installation accessories

Hazardous-location controllers and thermostats

Only hazardous-location control products are shown. Confirm the required class, division, group, temperature code, voltage, and load rating.