HSRL Hazardous-Location Self-Regulating Heat Trace
Chromalox HSRL5-2CT is low-temperature self-regulating cable for freeze protection and process maintenance in the specified Division 1 hazardous locations. It can be field cut up to its maximum circuit length.
Technical Specifications
- Series
- HSRL
- Manufacturer
- Chromalox
- Technology
- Self-Regulating
- Watt Density
- 5 W/ft at 50°F
- Nominal HEP Voltage
- 240 V
- Manufacturer Voltage
- 208–277 V
- Bus Wire
- Twin 16 AWG Copper
- Inner Jacket
- Polyolefin
- Braid
- Tinned Copper
- Outer Jacket
- High-Temperature Fluoropolymer Overjacket
- Maximum Maintain Temperature
- 150°F (65°C)
- Maximum Exposure, Power Off
- 185°F (85°C)
- Minimum Bend Radius
- 1-1/8 in
- Approximate Size
- 3/8 in W × 1/8 in H
- Pipe
- Metal & Plastic
- Cut to Length
- Yes
- Overlap
- Single overlap permitted
- Ground-Fault Protection
- Required; 30 mA minimum trip recommended
- Temperature Class
- T5
Output at Alternate Supply Voltages
| 208 V | 220 V | 277 V |
|---|---|---|
| 4.1 (-18%) W/ft | 4.5 (-10%) W/ft | 5.6 (+13%) W/ft |
Hazardous Location Approvals
FM Approved: Class I, Division 1, Groups B, C, D; Class II, Division 1, Groups E, F, G; Class III, Division 1.
CSA Approved: Class I, Division 1, Groups B, C, D; Class II, Division 1, Groups E, F, G.
Maximum Circuit Length
HSRL5-2CT — 240 V nominal, 5 W/ft
| Minimum Startup Temperature | 10 A | 15 A | 20 A | 25 A | 30 A | 40 A |
|---|---|---|---|---|---|---|
| 50°F | 250 ft | 375 ft | 505 ft | 540 ft | NR | NR |
| 0°F | 180 ft | 270 ft | 360 ft | 450 ft | 540 ft | NR |
| -20°F | 160 ft | 245 ft | 325 ft | 405 ft | 490 ft | 540 ft |
NR = Not Required; maximum circuit length is reached with a smaller breaker size. Maximum circuit length depends on breaker size and minimum startup temperature.
Construction
Twin 16 AWG copper bus wires are embedded in a semiconductive polymer self-regulating core. A polyolefin insulating jacket, tinned-copper grounding braid, and high-temperature fluoropolymer corrosion-resistant overjacket complete the construction.
HSRL Cable Selection
| Part Number | Output | HEP Nominal Voltage | Temperature Class |
|---|---|---|---|
| HSRL3-1CT | 3 W/ft | 120 V | T6 |
| HSRL3-2CT | 3 W/ft | 240 V | T6 |
| HSRL5-1CT | 5 W/ft | 120 V | T5 |
| HSRL5-2CTCurrent Product | 5 W/ft | 240 V | T5 |
| HSRL10-1CT | 10 W/ft | 120 V | T4A |
| HSRL8-2CT | 8 W/ft | 240 V | T5 |
| HSRL10-2CT | 10 W/ft | 240 V | T4A |
| HSRL8-1CT | 8 W/ft | 120 V | T5 |
Installation / Hazardous-Area Notes
- Cut to length in the field up to the applicable maximum circuit length.
- Use listed Chromalox HL connection components and ground the metallic braid.
- Provide code-compliant ground-fault protection; Chromalox recommends a 30 mA minimum trip level to reduce nuisance tripping.
- A single cable overlap is permitted without burnout.
For preliminary water-pipe freeze-protection sizing, use the Pipe Freeze Protection Configurator; Division 1 selection still requires engineering consultation.