2000 Series Self-Regulating Heat Trace
This 240 Volt cable supplies heat in direct response to local temperature changes for freeze protection and high-temperature process maintenance. It can be cut to length and terminated in the field without overheating or burning out when overlapped.
The 2025-21F00 uses stainless steel braid + fluoropolymer overjacket for its verified 2000 Series construction.
Technical Specifications
- Series
- 2000 Series
- SKU
- 2025-21F00
- Heat Output
- 25 Watt per Foot @ 50°F
- Metric Output
- 82 W/m @ 10°C
- Nominal Voltage
- 240 Volt
- Manufacturer Supply Range
- 208–277 VAC
- Cable Technology
- Self-Regulating
- Bus Wire
- Nickel-Coated Copper
- Conductive Core
- Modified Fluoropolymer
- Inner Jacket
- Modified Fluoropolymer
- Metallic Braid/Overshield
- Stainless Steel
- Outer Jacket
- Fluoropolymer
- Maximum Maintain Temperature
- 375°F (190°C)
- Maximum Intermittent Exposure
- 450°F (232°C)
- Temperature Rating
- T2C
- Cut to Length
- Yes
- Field Termination
- Yes
- Cable Overlap
- Permitted
- Ground-Fault Protection
- Required
Maximum Circuit Length
2025-21F00 — 240 V, 25 W/ft
| Minimum Startup Temperature | 15 A | 20 A | 30 A |
|---|---|---|---|
| 50°F | 90 ft | 120 ft | 170 ft |
| 0°F | 80 ft | 100 ft | 160 ft |
| -50°F | 80 ft | 100 ft | 160 ft |
Maximum circuit length depends on breaker size and minimum startup temperature.
Construction
Nickel-coated copper bus wires are embedded in a modified-fluoropolymer self-regulating conductive core. A modified-fluoropolymer inner jacket and stainless steel braid + fluoropolymer overjacket complete this configuration.
2000 Series Cable Selection
Compare the published 2000 Series bulk-cable constructions below. Select a part number to open that product.
Tinned Copper Braid
| Part Number | Output | Voltage |
|---|---|---|
| 2005-11C00 | 5 W/ft | 120 V |
| 2008-11C00 | 8 W/ft | 120 V |
| 2010-11C00 | 10 W/ft | 120 V |
| 2012-11C00 | 12 W/ft | 120 V |
| 2015-11C00 | 15 W/ft | 120 V |
| 2018-11C00 | 18 W/ft | 120 V |
| 2020-11C00 | 20 W/ft | 120 V |
| 2025-11C00 | 25 W/ft | 120 V |
| 2030-11C00 | 30 W/ft | 120 V |
| 2005-21C00 | 5 W/ft | 240 V |
| 2008-21C00 | 8 W/ft | 240 V |
| 2010-21C00 | 10 W/ft | 240 V |
| 2012-21C00 | 12 W/ft | 240 V |
| 2015-21C00 | 15 W/ft | 240 V |
| 2018-21C00 | 18 W/ft | 240 V |
| 2020-21C00 | 20 W/ft | 240 V |
| 2025-21C00 | 25 W/ft | 240 V |
| 2030-21C00 | 30 W/ft | 240 V |
Stainless Steel Braid
| Part Number | Output | Voltage |
|---|---|---|
| 2005-11S00 | 5 W/ft | 120 V |
| 2008-11S00 | 8 W/ft | 120 V |
| 2010-11S00 | 10 W/ft | 120 V |
| 2012-11S00 | 12 W/ft | 120 V |
| 2015-11S00 | 15 W/ft | 120 V |
| 2018-11S00 | 18 W/ft | 120 V |
| 2020-11S00 | 20 W/ft | 120 V |
| 2025-11S00 | 25 W/ft | 120 V |
| 2030-11S00 | 30 W/ft | 120 V |
| 2005-21S00 | 5 W/ft | 240 V |
| 2008-21S00 | 8 W/ft | 240 V |
| 2010-21S00 | 10 W/ft | 240 V |
| 2012-21S00 | 12 W/ft | 240 V |
| 2015-21S00 | 15 W/ft | 240 V |
| 2018-21S00 | 18 W/ft | 240 V |
| 2020-21S00 | 20 W/ft | 240 V |
| 2025-21S00 | 25 W/ft | 240 V |
| 2030-21S00 | 30 W/ft | 240 V |
Nickel-Plated Copper Braid
| Part Number | Output | Voltage |
|---|---|---|
| 2005-11K00 | 5 W/ft | 120 V |
| 2008-11K00 | 8 W/ft | 120 V |
| 2010-11K00 | 10 W/ft | 120 V |
| 2012-11K00 | 12 W/ft | 120 V |
| 2015-11K00 | 15 W/ft | 120 V |
| 2018-11K00 | 18 W/ft | 120 V |
| 2020-11K00 | 20 W/ft | 120 V |
| 2025-11K00 | 25 W/ft | 120 V |
| 2030-11K00 | 30 W/ft | 120 V |
| 2005-21K00 | 5 W/ft | 240 V |
| 2008-21K00 | 8 W/ft | 240 V |
| 2010-21K00 | 10 W/ft | 240 V |
| 2012-21K00 | 12 W/ft | 240 V |
| 2015-21K00 | 15 W/ft | 240 V |
| 2018-21K00 | 18 W/ft | 240 V |
| 2020-21K00 | 20 W/ft | 240 V |
| 2025-21K00 | 25 W/ft | 240 V |
| 2030-21K00 | 30 W/ft | 240 V |
Tinned Copper Braid + Fluoropolymer Overjacket
| Part Number | Output | Voltage |
|---|---|---|
| 2005-11T00 | 5 W/ft | 120 V |
| 2008-11T00 | 8 W/ft | 120 V |
| 2010-11T00 | 10 W/ft | 120 V |
| 2012-11T00 | 12 W/ft | 120 V |
| 2015-11T00 | 15 W/ft | 120 V |
| 2018-11T00 | 18 W/ft | 120 V |
| 2020-11T00 | 20 W/ft | 120 V |
| 2025-11T00 | 25 W/ft | 120 V |
| 2030-11T00 | 30 W/ft | 120 V |
| 2005-21T00 | 5 W/ft | 240 V |
| 2008-21T00 | 8 W/ft | 240 V |
| 2010-21T00 | 10 W/ft | 240 V |
| 2012-21T00 | 12 W/ft | 240 V |
| 2015-21T00 | 15 W/ft | 240 V |
| 2018-21T00 | 18 W/ft | 240 V |
| 2020-21T00 | 20 W/ft | 240 V |
| 2025-21T00 | 25 W/ft | 240 V |
| 2030-21T00 | 30 W/ft | 240 V |
Stainless Steel Braid + Fluoropolymer Overjacket
| Part Number | Output | Voltage |
|---|---|---|
| 2005-11F00 | 5 W/ft | 120 V |
| 2008-11F00 | 8 W/ft | 120 V |
| 2010-11F00 | 10 W/ft | 120 V |
| 2012-11F00 | 12 W/ft | 120 V |
| 2015-11F00 | 15 W/ft | 120 V |
| 2018-11F00 | 18 W/ft | 120 V |
| 2020-11F00 | 20 W/ft | 120 V |
| 2025-11F00 | 25 W/ft | 120 V |
| 2030-11F00 | 30 W/ft | 120 V |
| 2005-21F00 | 5 W/ft | 240 V |
| 2008-21F00 | 8 W/ft | 240 V |
| 2010-21F00 | 10 W/ft | 240 V |
| 2012-21F00 | 12 W/ft | 240 V |
| 2015-21F00 | 15 W/ft | 240 V |
| 2018-21F00 | 18 W/ft | 240 V |
| 2020-21F00 | 20 W/ft | 240 V |
| 2025-21F00Current Product | 25 W/ft | 240 V |
| 2030-21F00 | 30 W/ft | 240 V |
Nickel-Plated Copper Braid + Fluoropolymer Overjacket
| Part Number | Output | Voltage |
|---|---|---|
| 2005-11M00 | 5 W/ft | 120 V |
| 2008-11M00 | 8 W/ft | 120 V |
| 2010-11M00 | 10 W/ft | 120 V |
| 2012-11M00 | 12 W/ft | 120 V |
| 2015-11M00 | 15 W/ft | 120 V |
| 2018-11M00 | 18 W/ft | 120 V |
| 2020-11M00 | 20 W/ft | 120 V |
| 2025-11M00 | 25 W/ft | 120 V |
| 2030-11M00 | 30 W/ft | 120 V |
| 2005-21M00 | 5 W/ft | 240 V |
| 2008-21M00 | 8 W/ft | 240 V |
| 2010-21M00 | 10 W/ft | 240 V |
| 2012-21M00 | 12 W/ft | 240 V |
| 2015-21M00 | 15 W/ft | 240 V |
| 2018-21M00 | 18 W/ft | 240 V |
| 2020-21M00 | 20 W/ft | 240 V |
| 2025-21M00 | 25 W/ft | 240 V |
| 2030-21M00 | 30 W/ft | 240 V |
Installation Notes
- Cut and terminate in the field using compatible 2000 Series components.
- Use the applicable breaker and circuit-length table where manufacturer values are published.
- Ground the metallic braid or overshield.
- Provide ground-fault equipment protection as required.
Sizing water-pipe freeze protection? Use the Pipe Freeze Protection Configurator.