HTR Low-Temperature Self-Regulating Heat Trace
The 10HTR2-CT provides temperature-responsive heat for pipe freeze protection and low-temperature process maintenance. Its CT construction is suitable where a fluoropolymer overjacket is required.
Technical Specifications
- Series
- HTR
- SKU
- 10HTR2-CT
- Watt Density
- 10 W/ft at 50°F (10°C)
- Nominal Voltage
- 240 Volt
- Manufacturer Supply Voltage
- 220–240 VAC
- Cable Type
- Self-Regulating
- Bus Wire
- Tinned Copper, 14 AWG / 16 AWG
- Braid
- Tinned Copper
- Outer Jacket
- Fluoropolymer (CT)
- Maximum Maintenance Temperature
- 150°F (65°C)
- Intermittent Exposure Temperature
- 185°F (85°C)
- Temperature Classification
- T5/T6
- Minimum Bend Radius
- 30 mm
- Cut to Length
- Yes
- Field Termination
- Yes
- Cable Overlap
- Permitted
- Ground-Fault Protection
- Required
Maximum Circuit Length
10HTR2-CT — 240 V, 10 W/ft
| Minimum Startup Temperature | 16 A | 20 A | 25 A | 32 A | 40 A |
|---|---|---|---|---|---|
| 50°F (10°C) | 291 ft | 363 ft | 394 ft | 394 ft | 394 ft |
| 32°F (0°C) | 264 ft | 330 ft | 394 ft | 394 ft | 394 ft |
| 14°F (-10°C) | 242 ft | 302 ft | 377 ft | 394 ft | 394 ft |
| -4°F (-20°C) | 223 ft | 278 ft | 348 ft | 394 ft | 394 ft |
| -40°F (-40°C) | 193 ft | 242 ft | 302 ft | 387 ft | 394 ft |
Maximum circuit length depends on breaker size and minimum startup temperature.
Construction
Parallel tinned-copper bus wires and a PTC self-regulating conductive core are covered by modified-polyolefin inner insulation, tinned-copper braid, and a fluoropolymer overjacket.
HTR Cable Selection
Compare published CR thermoplastic and CT fluoropolymer HTR constructions.
| Part Number | Output | Voltage | Construction |
|---|---|---|---|
| 3HTR1-CR | 3 W/ft | 120 V | Tinned Copper Braid + Modified Polyolefin Overjacket (CR) |
| 3HTR2-CR | 3 W/ft | 240 V | Tinned Copper Braid + Modified Polyolefin Overjacket (CR) |
| 5HTR1-CR | 5 W/ft | 120 V | Tinned Copper Braid + Modified Polyolefin Overjacket (CR) |
| 5HTR2-CR | 5 W/ft | 240 V | Tinned Copper Braid + Modified Polyolefin Overjacket (CR) |
| 8HTR1-CR | 8 W/ft | 120 V | Tinned Copper Braid + Modified Polyolefin Overjacket (CR) |
| 8HTR2-CR | 8 W/ft | 240 V | Tinned Copper Braid + Modified Polyolefin Overjacket (CR) |
| 10HTR1-CR | 10 W/ft | 120 V | Tinned Copper Braid + Modified Polyolefin Overjacket (CR) |
| 10HTR2-CR | 10 W/ft | 240 V | Tinned Copper Braid + Modified Polyolefin Overjacket (CR) |
| 12HTR1-CR | 12 W/ft | 120 V | Tinned Copper Braid + Modified Polyolefin Overjacket (CR) |
| 12HTR2-CR | 12 W/ft | 240 V | Tinned Copper Braid + Modified Polyolefin Overjacket (CR) |
| 3HTR1-CT | 3 W/ft | 120 V | Tinned Copper Braid + Fluoropolymer Overjacket (CT) |
| 3HTR2-CT | 3 W/ft | 240 V | Tinned Copper Braid + Fluoropolymer Overjacket (CT) |
| 5HTR1-CT | 5 W/ft | 120 V | Tinned Copper Braid + Fluoropolymer Overjacket (CT) |
| 5HTR2-CT | 5 W/ft | 240 V | Tinned Copper Braid + Fluoropolymer Overjacket (CT) |
| 8HTR1-CT | 8 W/ft | 120 V | Tinned Copper Braid + Fluoropolymer Overjacket (CT) |
| 8HTR2-CT | 8 W/ft | 240 V | Tinned Copper Braid + Fluoropolymer Overjacket (CT) |
| 10HTR1-CT | 10 W/ft | 120 V | Tinned Copper Braid + Fluoropolymer Overjacket (CT) |
| 10HTR2-CTCurrent Product | 10 W/ft | 240 V | Tinned Copper Braid + Fluoropolymer Overjacket (CT) |
| 12HTR1-CT | 12 W/ft | 120 V | Tinned Copper Braid + Fluoropolymer Overjacket (CT) |
| 12HTR2-CT | 12 W/ft | 240 V | Tinned Copper Braid + Fluoropolymer Overjacket (CT) |
Installation Notes
- Cut and terminate in the field using compatible HTR connection and termination components.
- Use the applicable circuit-length table for the selected startup temperature and Type C breaker.
- Ground the metallic braid and provide code-compliant ground-fault protection.
- Cable overlap is permitted by the HTR manufacturer.
Sizing water-pipe freeze protection? Use the Pipe Freeze Protection Configurator.