10 Watt per Foot 120 Volt Self-Regulating Heat Trace Cable – Thermoplastic Overjacket over Metal Braid – HTR

Part Number: 10HTR1-CR

In Stock: 10,300 FT

$5.42 per ft

Installation Kits, Accessories & ControllersInstallation Kits, Accessories & Controllers →
Freeze Protection Configurator

Build a complete freeze-protection system for water piping.

120 Volt, 10 Watt per Foot self-regulating heat trace cable with tinned copper braid and modified-polyolefin thermoplastic overjacket. For pipe freeze protection and low-temperature process maintenance up to 150°F. Cut to length in the field.

Wattage
10 Watt
Buy 1000' $4.82
Buy 5000' $4.34

Enter how many feet you want to order. Cable is cut to length.

HTR Low-Temperature Self-Regulating Heat Trace

The 10HTR1-CR provides temperature-responsive heat for pipe freeze protection and low-temperature process maintenance. Its CR construction uses a modified-polyolefin thermoplastic overjacket for general industrial environments.

Technical Specifications

Series
HTR
SKU
10HTR1-CR
Watt Density
10 W/ft at 50°F (10°C)
Nominal Voltage
120 Volt
Manufacturer Supply Voltage
110–120 VAC
Cable Type
Self-Regulating
Bus Wire
Tinned Copper, 14 AWG / 16 AWG
Braid
Tinned Copper
Outer Jacket
Modified Polyolefin Thermoplastic (CR)
Maximum Maintenance Temperature
150°F (65°C)
Intermittent Exposure Temperature
185°F (85°C)
Temperature Classification
T5/T6
Minimum Bend Radius
30 mm
Cut to Length
Yes
Field Termination
Yes
Cable Overlap
Permitted
Ground-Fault Protection
Required

Maximum Circuit Length

10HTR1-CR — 120 V, 10 W/ft

Minimum Startup Temperature 16 A 20 A 25 A 32 A 40 A
50°F (10°C) 145 ft 182 ft 197 ft 197 ft 197 ft
32°F (0°C) 132 ft 165 ft 197 ft 197 ft 197 ft
14°F (-10°C) 121 ft 151 ft 189 ft 197 ft 197 ft
-4°F (-20°C) 111 ft 139 ft 174 ft 197 ft 197 ft
-40°F (-40°C) 97 ft 121 ft 151 ft 193 ft 197 ft

Maximum circuit length depends on breaker size and minimum startup temperature.

Construction

Parallel tinned-copper bus wires and a PTC self-regulating conductive core are covered by modified-polyolefin inner insulation, tinned-copper braid, and a modified-polyolefin thermoplastic overjacket.

HTR Cable Selection

Compare published CR thermoplastic and CT fluoropolymer HTR constructions.

Part Number Output Voltage Construction
3HTR1-CR 3 W/ft 120 V Tinned Copper Braid + Modified Polyolefin Overjacket (CR)
3HTR2-CR 3 W/ft 240 V Tinned Copper Braid + Modified Polyolefin Overjacket (CR)
5HTR1-CR 5 W/ft 120 V Tinned Copper Braid + Modified Polyolefin Overjacket (CR)
5HTR2-CR 5 W/ft 240 V Tinned Copper Braid + Modified Polyolefin Overjacket (CR)
8HTR1-CR 8 W/ft 120 V Tinned Copper Braid + Modified Polyolefin Overjacket (CR)
8HTR2-CR 8 W/ft 240 V Tinned Copper Braid + Modified Polyolefin Overjacket (CR)
10HTR1-CRCurrent Product 10 W/ft 120 V Tinned Copper Braid + Modified Polyolefin Overjacket (CR)
10HTR2-CR 10 W/ft 240 V Tinned Copper Braid + Modified Polyolefin Overjacket (CR)
12HTR1-CR 12 W/ft 120 V Tinned Copper Braid + Modified Polyolefin Overjacket (CR)
12HTR2-CR 12 W/ft 240 V Tinned Copper Braid + Modified Polyolefin Overjacket (CR)
3HTR1-CT 3 W/ft 120 V Tinned Copper Braid + Fluoropolymer Overjacket (CT)
3HTR2-CT 3 W/ft 240 V Tinned Copper Braid + Fluoropolymer Overjacket (CT)
5HTR1-CT 5 W/ft 120 V Tinned Copper Braid + Fluoropolymer Overjacket (CT)
5HTR2-CT 5 W/ft 240 V Tinned Copper Braid + Fluoropolymer Overjacket (CT)
8HTR1-CT 8 W/ft 120 V Tinned Copper Braid + Fluoropolymer Overjacket (CT)
8HTR2-CT 8 W/ft 240 V Tinned Copper Braid + Fluoropolymer Overjacket (CT)
10HTR1-CT 10 W/ft 120 V Tinned Copper Braid + Fluoropolymer Overjacket (CT)
10HTR2-CT 10 W/ft 240 V Tinned Copper Braid + Fluoropolymer Overjacket (CT)
12HTR1-CT 12 W/ft 120 V Tinned Copper Braid + Fluoropolymer Overjacket (CT)
12HTR2-CT 12 W/ft 240 V Tinned Copper Braid + Fluoropolymer Overjacket (CT)

Installation Notes

  • Cut and terminate in the field using compatible HTR components.
  • Use the applicable circuit-length table and ground the metallic braid.
  • Provide code-compliant ground-fault protection. Cable overlap is manufacturer permitted.

Sizing water-pipe freeze protection? Use the Pipe Freeze Protection Configurator.

Complete the Cable System

Connection, termination, installation, and control products selected for HTR Series cable. Verify electrical ratings and installation requirements for the exact circuit.

Connection and installation accessories

Controllers and thermostats

Choose ambient or line sensing and confirm voltage, circuit load, sensor, enclosure, and ground-fault requirements.