10 Watt per Foot 240 Volt Self-Regulating Heat Trace Cable – Fluoropolymer Overjacket – HTS

Part Number: 10HTS2-CT

In Stock: 1,209 FT

$16.50 per ft

Installation Kits, Accessories & ControllersInstallation Kits, Accessories & Controllers →
Freeze Protection Configurator

Build a complete freeze-protection system for water piping.

240 Volt, 10 Watt per Foot self-regulating heat trace cable with tinned copper braid and high-temperature fluoropolymer overjacket. For freeze protection and process maintenance up to 302°F where elevated temperature capability is required. Cut to length in the field.

Watt Density
10 W/ft
Voltage
240 V

Enter how many feet you want to order. Cable is cut to length.

HTS High-Temperature Self-Regulating Heat Trace

10HTS2 provides self-regulating heat for industrial freeze protection and process-temperature maintenance where elevated cable temperature capability is required.

Technical Specifications

Series
HTS
SKU
10HTS2
Watt Density
10 W/ft at 50°F (10°C)
Nominal Voltage
240 V
Manufacturer Voltage
220–240 VAC
Cable Technology
Self-Regulating
Bus Wires
Nickel-Plated Copper, 16 AWG
Conductive Core
PTC Semiconductive Polymer
Inner Jacket
Fluoropolymer
Metallic Braid
Tinned Copper
Outer Jacket
Fluoropolymer (CT)
Maximum Maintain Temperature
302°F (150°C)
Maximum Continuous Exposure, Power Off
392°F (200°C)
Temperature Class
T3
Minimum Bend Radius
30 mm
Minimum Installation Temperature
-76°F (-60°C)
Ingress Protection
IP66/67
Cut to Length
Yes
Field Termination
Yes
Cable Overlap
Permitted
Ground-Fault Protection
Required

Maximum Circuit Length

10HTS2 — 240 V, 10 W/ft

Minimum Startup Temperature 16 A 20 A 25 A 32 A 40 A
50°F (10°C) 294 ft 366 ft 421 ft 421 ft 421 ft
32°F (0°C) 264 ft 339 ft 407 ft 421 ft 421 ft
14°F (-10°C) 240 ft 308 ft 380 ft 421 ft 421 ft
-4°F (-20°C) 209 ft 281 ft 325 ft 401 ft 421 ft
-40°F (-40°C) 178 ft 229 ft 283 ft 370 ft 421 ft

Maximum circuit length depends on breaker size and minimum startup temperature.

Construction

Parallel nickel-plated copper bus wires and a PTC self-regulating conductive core are covered by fluoropolymer inner insulation, tinned-copper braid, and a red fluoropolymer CT overjacket. The jacket supports the family’s elevated temperature and environmental capability.

HTS Cable Selection

Part Number Output Voltage Construction
5HTS1 5 W/ft 120 V CT Fluoropolymer Overjacket
10HTS1 10 W/ft 120 V CT Fluoropolymer Overjacket
15HTS1 15 W/ft 120 V CT Fluoropolymer Overjacket
20HTS1 20 W/ft 120 V CT Fluoropolymer Overjacket
5HTS2 5 W/ft 240 V CT Fluoropolymer Overjacket
10HTS2Current Product 10 W/ft 240 V CT Fluoropolymer Overjacket
15HTS2 15 W/ft 240 V CT Fluoropolymer Overjacket
20HTS2 20 W/ft 240 V CT Fluoropolymer Overjacket

Installation Notes

  • Cut and terminate in the field with components specifically rated and approved for HTS cable.
  • Use the applicable circuit-length table and ground the metallic braid.
  • Provide code-compliant ground-fault protection.
  • Cable overlap is permitted by the manufacturer.

Sizing water-pipe freeze protection? Use the Pipe Freeze Protection Configurator.

Complete the Cable System

Connection, termination, installation, and control products selected for HTS Series cable. Verify electrical ratings and installation requirements for the exact circuit.

Connection and installation accessories

Controllers and thermostats

Choose ambient or line sensing and confirm voltage, circuit load, sensor, enclosure, and ground-fault requirements.