Overview
CPR-10-1CR is a self-regulating commercial heat-trace cable. As pipe temperature falls, the conductive polymer core increases heat output; as temperature rises, output decreases. The cable can be field cut to the required length within the documented maximum circuit-length limit for the application and electrical conditions.
This Model
| SKU | CPR-10-1CR |
|---|---|
| Nominal output | 10 W/ft at 50°F |
| Voltage family | 120 V |
| Outer jacket | CR — TPE overjacket over braid for protection against certain inorganic chemical solutions |
| Approximate cable size | 0.47 in W × 0.20 in H |
| Minimum bend radius | 1-1/8 in |
| Maximum process maintenance | 150°F / 65°C, power on |
| Maximum continuous exposure | 185°F / 85°C, power off |
| Buying format | Sold by the foot |
Fire Sprinkler Pipe Freeze Protection
This exact CPR10 model is in the documented Fire Sprinkler Pipe Freeze Protection cable family when selected from the published tables and installed on metallic piping with the required approved connections, controls, sensors, attachment accessories, insulation and cover. The sprinkler listing does not extend to plastic piping.
Typical Supported Applications
- Commercial pipe freeze protection for potable and non-potable piping
- Sanitary, storm, greasy-waste and diesel-fuel piping where the selected system is suitable
- Fire-sprinkler piping under the sprinkler-specific limits above
- Roof and gutter de-icing
- Freezer frost-heave prevention and floor warming where designed for that application
Application-specific design and circuit limits differ. Do not reuse a circuit table from another application.
Cable Construction
- 16 AWG nickel-plated copper bus conductors carry the circuit current.
- Self-regulating polymer matrix changes resistance and heat output with local temperature.
- Flame-retardant polyolefin primary jacket electrically insulates the heating matrix and provides documented water/inorganic-solution resistance.
- Tinned-copper braid adds mechanical protection and provides a grounding path.
- CR outer jacket — TPE overjacket over braid for protection against certain inorganic chemical solutions.
Do not broaden chemical compatibility beyond the supplied datasheet; confirm the actual exposure before selecting CR or CT.
Electrical Design
Maximum circuit length varies by CPR wattage, voltage family, breaker rating, startup temperature and application. Ground-fault equipment protection is required. For sprinkler work, use the fire-sprinkler-specific design tables rather than the generic CPR pipe-freeze, roof/gutter or grease-maintenance tables.
Required System Components
A complete sprinkler installation requires compatible power connection, tee/splice components where the route branches or joins, approved end seals, the documented ITC-FS/RTBC-FS control and overtemperature system, sensors, fiberglass attachment tape, warning labels, and non-combustible insulation with a sealed non-combustible exterior cover.
Selection information does not replace product installation instructions, electrical design, or fire-protection engineering.