1¼” Steel NPT Screw Plug Heater – 20–23 WSI – 3 Element

Part Number: PTFM2

Availability: Built to order — typically ships in 2–4 weeks

$592.11

1¼ in NPT Steel screw-plug immersion heater with 3 elements, 20-23 W/in² nominal watt density, 500–3,000 W selectable output, and 120/240 VAC configurations. Select options to generate the finished ProTherm part number.

Configured Part NumberSelect heater configuration to determine part number.

Product total
Options total
Grand total

This ProTherm 1¼ in NPT screw-plug immersion heater uses a Steel plug, 3 heating elements, and a nominal 20-23 W/in² watt-density family. It is configured to order through the selections above; the validated combination determines the finished ProTherm PT part number.

Technical specifications

Base family SKU PTFM2
NPT connection 1¼ in NPT
Screw-plug material Steel
Element sheath Incoloy 840
Nominal watt density 20-23 W/in²
Element count 3
Available output 500–3,000 W
Available voltage 120 / 240 VAC
Phase Single phase
Selectable immersion range 6 ¼–36 ⅝ in
Standard enclosure NEMA 1; configured enclosure and thermostat options are shown above
Terminals #10-32 plate terminals with screws
Published plug dimensions E 1⅜ in; F 9⁄16 in; H 1¾ in

Dimensional reference

1¼ in NPT ProTherm screw plug heater dimensional reference
Reference drawing for the 1¼ in NPT product group. Dimension B is the selected immersed length. Use the configured selection and approved order documentation for final installation dimensions.

E, F and H plug dimensions

Plug material E F H
Brass 1¼ in 3⁄8 in 1¾ in
Steel or stainless steel 1⅜ in 9⁄16 in 1¾ in

Construction and features

  • Incoloy 840 element sheath with high-purity compacted magnesium oxide insulation.
  • Nickel-chromium resistance wire and fusion-welded pin-to-resistance-wire junction.
  • The Incoloy 840 elements are welded to the steel screw plug for joint strength and corrosion protection.
  • Moisture-sealed element ends; sealing construction is selected for the intended medium.
  • Accessible NEMA 1 terminal housing with fixed conduit support.
  • Spacer supports are used on applicable multiple-element units with longer immersed lengths.
  • Applicable units may be configured with thermostat, thermowell, and alternate enclosure options shown in the product selector.

Typical applications

  • Oils and compatible alkali solutions
  • Reservoirs, process tanks, and industrial equipment requiring lower surface loading

Why watt density matters

This lower-watt-density family reduces surface loading and is intended for media such as oils or other temperature-sensitive services when compatibility is confirmed. Watt density is one part of heater selection; also verify sheath and plug compatibility, liquid level, circulation, operating temperature, and controls.

Configuration

Select the required output or immersion length, voltage, and available terminal-housing or control options using the configurator above. HEP’s explicit mapping validates the combination and displays the finished ProTherm part number; the family SKU is not the finished ordering number.

Engineering and application support

Confirm chemical compatibility, allowable watt density, required immersion, voltage, phase, enclosure rating, and control strategy before installation. Keep the heated section immersed during operation. For uncertain media or non-standard requirements, use the Screw Plug Heater Engineering Selector or contact HEP Engineering.