8 Watt Low Temp Self-Regulating Heating Cable - 8HTR
- Buy 1000 for $4.82 each and save 11%
- Buy 5000 for $4.34 each and save 20%
Cut-to-length self-regulating heating cable (HTR) is ideal for freeze protection and low temperature process maintenance up to 150°F.
8 W/ft
120 or 240 V
TPE or Fluropolymer Jacket
Maximum Continuous Maintenance Temperature: 150°F (65°C)
Intermittent Exposure Temperature Range: -40°F to 185°F (-40°C to 85°C)
Supply Voltage: 110-120 VAC or 208-277 VAC
Nominal Power Output at 50°F (10°C):
- 3, 5, 8, 10, 12 watts/ft (10, 16, 26, 33, 39 watts/m)
- For 208 and 277 VAC, adjust watts shown for the 240 VAC cable using the Voltage Adjustment Factors chart
Bus Wire Gauge: 16 AWG
Braid Resistance: Tinned copper 0.0055 ohms/ft (0.0182 ohms/m)
T-Rating:
- T6: 3, 5, 8, 10 watts/ft (10, 16, 26, 33 watts/m)
- T5: 12 watts/ft (39 watts/m)
Bend Radius: 0.5 in (12 mm)
NOTE: Electrical equipment T-Rating codes define the maximum surface temperature that equipment will reach. It is used in hazardous (classified) area applications.
- Ordinary Locations
- Ordinary Locations
- Hazardous Location
-
-
- Class I Division 2 Groups A, B, C, D
- Class II Division 2 Groups E, F, G
- Class III
-
Approval valid only when used with appropriate heating cable and installation accessories, and installed in accordance with all applicable instructions, codes, and regulations.